- General Information
- Payload Table
Trapezoidal Plates can be produced from galvanized sheet or aluminum, with or without coilcoating paint, in different thicknesses. It is used in single layer without thermal insulation or multi-layer roof and wall applications with thermal insulation laid between two trapezoids.
In systems applied by insulating between two trapezoids, distance determining purlins are used between them. A vapor barrier should be used to prevent water vapor and condensation that may come from inside the lower trapezoid. The intermediate purlin, and therefore the upper load of the roof, must be transferred to the carrier construction of the building by means of flat bars, without loading the lower trapezoid. At least 1 llama should be used on Mt. EPS, XPS, Polyurethane, Rockwool and Glasswool plates are used as thermal insulation.
In mineral wool thermal insulation, a vapor balancer should be used on the upper surface of the plate. Thermal bridges between distance adjusting profiles and trapezoids should be prevented with insulation tapes.
| Product Name |
Metal Thickness (mm) |
Panel Weight (kg/m2) |
Span (mm) |
Pearl Range | ||||
|---|---|---|---|---|---|---|---|---|
| 1000 | 1500 | 2000 | 2500 | 3000 | ||||
| Max.Spread Load (kg/m2) | ||||||||
| 32/250 Trapeze |
0.40 | 3.77 | Two Span | 341 | 208 | 108 | 58 | 51 |
| Three Span | 393 | 242 | 128 | 70 | 63 | |||
| 0.50 | 4.71 | Two Span | 421 | 258 | 135 | 72 | 63 | |
| Three Span | 485 | 297 | 162 | 90 | 77 | |||
| 0.60 | 5.65 | Two Span | 489 | 312 | 163 | 87 | 76 | |
| Three Span | 558 | 356 | 194 | 106 | 94 | |||
| 0.70 | 6.59 | Two Span | 562 | 364 | 190 | 101 | 91 | |
| Three Span | 641 | 415 | 230 | 124 | 112 | |||
Notes:
. “Safety Stress” method was used in the calculations. Self-weight, live load (wind load) and temperature change (Δt=±20ºC) are taken into account.
. The deflection limit is taken as L/200 and L/150 if the loads act as pressure, and L/150 if the loads act as suction.
. Sheet quality is based on fγ=240 Mpa (Yield Strength).
Technical documents