MP-32/250 Roof and Facade Trapezoid

System code
MP-32/250
Application
Trapezoidal sheets
Insulation / group
PUR insulated
Data status
Recovered from archive
Source pages
2
  • General Information
  • Payload Table

Trapezoidal Plates can be produced from galvanized sheet or aluminum, with or without coilcoating paint, in different thicknesses. It is used in single layer without thermal insulation or multi-layer roof and wall applications with thermal insulation laid between two trapezoids.

In systems applied by insulating between two trapezoids, distance determining purlins are used between them. A vapor barrier should be used to prevent water vapor and condensation that may come from inside the lower trapezoid. The intermediate purlin, and therefore the upper load of the roof, must be transferred to the carrier construction of the building by means of flat bars, without loading the lower trapezoid. At least 1 llama should be used on Mt. EPS, XPS, Polyurethane, Rockwool and Glasswool plates are used as thermal insulation.

In mineral wool thermal insulation, a vapor balancer should be used on the upper surface of the plate. Thermal bridges between distance adjusting profiles and trapezoids should be prevented with insulation tapes.

Technical illustration
Product Name
 
Metal Thickness
(mm)
Panel Weight
(kg/m2)
Span
(mm)
Pearl Range
1000 1500 2000 2500 3000
Max.Spread Load (kg/m2)
32/250
Trapeze
0.40 3.77 Two Span 341 208 108 58 51
Three Span 393 242 128 70 63
0.50 4.71 Two Span 421 258 135 72 63
Three Span 485 297 162 90 77
0.60 5.65 Two Span 489 312 163 87 76
Three Span 558 356 194 106 94
0.70 6.59 Two Span 562 364 190 101 91
Three Span 641 415 230 124 112

Notes:
. “Safety Stress” method was used in the calculations. Self-weight, live load (wind load) and temperature change (Δt=±20ºC) are taken into account.
. The deflection limit is taken as L/200 and L/150 if the loads act as pressure, and L/150 if the loads act as suction.
. Sheet quality is based on fγ=240 Mpa (Yield Strength).